Customization: | Available |
---|---|
After-sales Service: | Yes 24 Hours Online Service |
Warranty: | 1 Year |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
S8500 Gas Alarm Controller | |
Installation method | Indoor wall-mounted |
Response time | ≤10s |
Instruction mode | color LCD display, sound and light alarm |
Working environment temperature | -10ºC~50ºC |
Working environment humidity | ≤95%RH |
Main power supply | AC220V±15%, 50Hz±1% |
Standby power supply | two DC12V/2.3AH rechargeable batteries connected in series |
No-load power | ≤10W |
Detector power supply voltage | DC24V±10% |
Backup battery undervoltage alarm value | DC21V±1V |
Dimensions | L420×W270×H107 mm |
Controller and detector connection line requirements | ≥RVVP 3×1.52mm |
Communication distance between controller and detector | ≤1000m |
Number of controller channels | 5 channels |
Controller connection type | Point type combustible gas detector outputting standard 485 signal |
Passive switch | 6-way passive switch capacity 2A/AC220V |
Maximum measuring range | 100% LEL |
Minimum accuracy | 1% LEL |
Alarm record storage; | >30000 records (with memory card) |